ANSI 1.2kV 250A Transformer Bushing
High Current Low Voltage Porcelain Bushing | 30kV Lightning Impulse Withstand | ANSI C76
Rated Voltage: 1.2 kV | Rated Current: 250 A | Creepage Distance: ≥25 mm | BIL: 30 kV
This ANSI standard low voltage transformer bushing is designed for the LV side of larger distribution transformers, pad-mounted transformers, and substation auxiliary transformers requiring higher current capacity. Rated at 1.2kV and 250A continuous current, it shares the same high insulation withstand characteristics as the 125A version: lightning impulse withstand of 30kV and dry power-frequency withstand of 10kV. The robust porcelain insulator and flange mount design ensure oil-tight installation, UV resistance, and long service life. Direct OEM replacement for standard 1.2kV 250A bushings.
Designed for compatibility and durability, this bushing is ideal for a wide range of transformers used in commercial buildings, industrial plants, and power distribution units. Its standard design facilitates easy installation and replacement, minimizing downtime.
As a professional manufacturer of porcelain insulator and porcelain bushing, we offer good quality and low price porcelain bushing for transformer and capacitor and switch.

Technical Specifications
| Parameter | Value |
|---|---|
| Rated Voltage | 1.2 kV |
| Rated Current | 250 A |
| Creepage Distance | ≥25 mm |
| Lightning Impulse Withstand Voltage (BIL) | 30 kV peak (1.2/50μs waveform) |
| Power-Frequency Withstand Voltage (Dry) | 10 kV rms (1 minute) |
| Applicable Standard | ANSI C76 / IEEE C57.19.01 |
| Insulation Material | Wet-process porcelain (high-grade) |
| Mounting Type | Flange mount with gasket groove |
| Terminal Type | Pad connector (standard – 2 holes) / Heavy-duty stud (optional) |
| Gasket Material | Neoprene (standard) / Silicone (optional) |
| Installation Orientation | Vertical or horizontal (within 15°) |
| Ambient Temperature Range | -40°C to +55°C |
| Altitude | Up to 1000m (derating above) |
Electrical Withstand Capability – Engineering Summary
| Test Type | Applied Voltage | Duration / Waveform | Result Requirement |
|---|---|---|---|
| Lightning Impulse Withstand | 30 kV peak | 1.2/50 μs | No flashover or puncture |
| Power-Frequency Dry Withstand | 10 kV rms | 1 minute | No breakdown |
| Leak Test (Flange Seal) | 50 kPa air pressure | 1 minute | No leakage |
Key Engineering Features
ANSI C76 / IEEE C57.19.01 compliant – Full compliance for North American utility and industrial applications
250A continuous current – Suitable for larger LV windings and higher kVA transformers
30kV BIL – Standard impulse withstand for 1.2kV class exposed bushings (per ANSI C57.12.00)
≥25mm creepage distance – Meets minimum requirements for normal pollution environments
10kV dry withstand – Verified insulation strength under clean, dry conditions
Wet-process porcelain – Non-porous, high tracking resistance, excellent outdoor durability
Heavy-duty terminal – Pad connector standard (2-hole NEMA pattern) for secure high-current connection
Flange mount with gasket groove – Oil-tight seal on transformer tank cover or wall
-40°C to +55°C operation – Reliable performance across extreme temperature ranges
Dimensional Data (Typical – Confirm with Datasheet)
| Dimension | Typical Value (mm) | Typical Value (inches) |
|---|---|---|
| Overall Length | 170 – 200 mm | 6.7 – 7.9 in |
| Flange Diameter | 85 – 95 mm | 3.3 – 3.7 in |
| Flange Bolt Circle | 65 – 75 mm | 2.6 – 3.0 in |
| Mounting Holes | 4 holes, 8mm or 10mm diameter | 5/16″ or 3/8″ |
| Creepage Distance (external) | ≥25 mm | ≥1.0 in |
| Terminal Pad (standard) | 2 holes, 25mm spacing | 1 inch spacing (NEMA pattern) |
Note: The 250A bushing typically has a slightly larger flange and terminal pad than the 125A version. For certified dimensional drawings, request the product datasheet.

Features & Benefits:
ANSI Standard Compliance: Guarantees interoperability, reliability, and adherence to recognized industry specifications for consistent performance.
Optimized for 1.2KV / 250A: Precisely engineered for medium-voltage, mid-current applications, providing a perfect balance of safety and efficiency.
High-Grade Porcelain Construction: Offers excellent dielectric properties, high mechanical strength, and outstanding resistance to environmental factors like moisture and pollution.
Proven Durability: The ceramic material ensures thermal stability and a long service life with minimal maintenance requirements.
Versatile Application: Suitable for power transformers, distribution transformers, and other electrical equipment requiring a reliable medium-voltage bushing solution.
Compliance & Testing
Each 1.2kV 250A transformer bushing is factory tested per ANSI C76. A Factory Acceptance Test Report (FAT) is included with each shipment, covering:
Visual and mechanical inspection
Dimensional verification (critical mounting and sealing dimensions)
Power-frequency dry withstand test (10kV, 1 minute)
Lightning impulse withstand test (30kV, 1.2/50μs, 3 positive and 3 negative impulses)
Flange seal leak test (50kPa air pressure, 1 minute)
Porcelain surface integrity check (dye penetrant on sample basis)
Terminal connection resistance measurement (for pad connector version)
Third-party witness testing: SGS, TÜV, Bureau Veritas, or Intertek – available upon request.
Ordering Information
To place an order or request a quote, please specify:
| Ordering Parameter | Options |
|---|---|
| Rated Current | 250A (fixed for this model) |
| Rated Voltage | 1.2kV (fixed) |
| Terminal Type | Pad connector (2-hole, 1″ spacing) / Heavy-duty stud (specify thread) |
| Gasket Material | Neoprene (standard) / Silicone / Viton |
| Quantity | Single piece / 10 pieces / 50 pieces / 100+ pieces |
| Packaging | Standard export carton / Palletized |
| Certification Required | Standard FAT / Third-party inspection (specify agency) |
Typical lead time: 15–30 days depending on quantity (stock units may be available)
Typical Applications
Low voltage side of larger distribution transformers (500kVA – 2500kVA range, 1.2kV LV)
Pad-mounted transformers requiring 250A LV termination
Substation station service transformers with higher auxiliary loads
Industrial control transformers (1.2kV primary or secondary)
Transformer repair and maintenance – direct OEM replacement for 250A LV bushings
Re-bushing projects upgrading from 125A to 250A (check flange compatibility)
Cross-Reference Information
This bushing is dimensionally compatible with standard 1.2kV 250A bushings originally supplied on:
ABB / Cooper (formerly McGraw-Edison)
ERMCO (larger pad-mounted units)
Eaton (Cooper Power series – 250A LV)
Siemens (medium distribution transformers)
Delta Star
Virginia Transformer (250A LV termination)
For cross-reference verification, please provide the OEM part number or a sample drawing.
Comparison Table – 125A vs 250A Models
| Parameter | 125A Model | 250A Model |
|---|---|---|
| Rated Voltage | 1.2 kV | 1.2 kV |
| Rated Current | 125 A | 250 A |
| Creepage Distance | ≥25 mm | ≥25 mm |
| Lightning Impulse Withstand | 30 kV | 30 kV |
| Power-Frequency Dry Withstand | 10 kV | 10 kV |
| Typical Flange Diameter | 75–85 mm | 85–95 mm |
| Standard Terminal | Plain stud (M10 / 3/8″) | Pad connector (2-hole) |
| Typical Application | Smaller transformers (≤500kVA) | Larger transformers (500–2500kVA)
|